  • Nguồn lưu điện UPS VERTIV GXT5-2000IRT2UXL (01202010)– Liebert GXT5 On-Line 2000VA/2000W 230V LCD PF1.0 2U Extended Run Rack/Tower, Rail Kit Bundled.

    – Công nghệ: On-line Double Conversion.

    – Điện áp đầu vào: 230VAC.

    – Tần số nguồn vào: 40Hz-70Hz.

    – Điện áp đầu ra: 200/208/220/230/240 VAC.

    – Kích thước: 470 × 430 × 85 cm.

    – Trọng lượng: 21kg.

THÔNG TIN KỸ THUẬT:

Ratings (VA/W) 2000VA/ 2000W
Dimensions and Weight
Dimensions (D × W × H) 470 × 430 × 85 mm
Weight 21kg
Input
Rated Volatge 230 VAC
Rated Frequency 50 Hz / 60 Hz
Frequency Range 40 to 70 Hz
Power Factor ≥0.99
Input Power Cord C20
Output
Nominal Voltage 200/208/220/230/240 VAC
Waveform Sine wave
Inverter Overload Capability >200% minimum 250 ms, 150 to 200% for 2 seconds; 125 to 150% for 50 seconds; 105 to 125% for 60 seconds
Efficiency in Online Mode Up to 93%
Active Eco Mode Up to 98%
Output Receptacles (8) EN60320/C13
Internal Battery
Rated Voltage 48 Vdc
Charger Current Nominal 2.2 A; Maximum 8 A
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating 4 x 12 V x 9.0 Ah
End Cell Voltage 1.67 V/cell (discharge voltage per cell will be from 1.67 Vdc to 1.90 Vdc, canbe selected by PARAMSET)
Floating Voltage Equalize charge: 2.35 V/cell; Float charge: 2.27 V/cell
Battery Voltage Range  40 Vdc to 56.4 Vdc
General
Operating Temperature, °C Full power up to 40 ºC (up to 50 ºC with derating)
Storage Temperature, °C -20 to 60 ( contain batteries will be from -15 to 40 °C.)
Relative Humidity 0 to 95% non-condensing
Operating Elevation Up to 3,000 m at 25°C without derating
Audible Noise
Safety UL-1778 (Fifth Edition), C-UL listed, IEC 62040-1: 2008 (First Edition) + Am 1:2013, EN 62040-1:2008+A1:2013
RFI/EMI CISPR22 Class A (RFI)/ FCC Part 15 (Class A)
Transportation ISTA Procedure 1A
Surge Immunity ANSI C62.41 Category B

– Xuất xứ: Trung Quốc.